42 Month Warranty
| Description | Power Smart HF00-SQPROAL1200 | |||||||
|---|---|---|---|---|---|---|---|---|
| Nominal Battery Voltage | 12V | |||||||
| Back-Up Mode | ||||||||
| Output Wave Form | Pure Sine Wave | |||||||
| No Load Output Voltage | 220V ± 7V AC | |||||||
| Output Frequency | 50Hz ± 1Hz | |||||||
| No Load Battery Current | ≤ 2.0 AMP | ≤ 1.2 AMP | ||||||
| Full Load Output Current ± 1Amp | 59 AMP | 46 AMP | 64 AMP | 105 AMP | 49 AMP | 56 AMP | 49 AMP | 59 AMP | 
| Total Harmonics Distortion (@ Linear Load) | < 3% | |||||||
| Battery Low Pre-Alarm | 10.8V ≤ 0.2V / Battery (12V DC of each battery) | |||||||
| Battery Low Cut Off | 10.5V ≤ 0.2V / Battery (12V DC of each battery) | |||||||
| Mains Mode | ||||||||
| Max. Charging Current (HC) | 15A ± 1A | 15A ± 1A | 15A ± 1A | 22A ± 1A | 15A ± 1A | 18A ± 1A | 18A ± 1A | 18A ± 1A | 
| Max. Charging Current (NC) | 12A ± 1A | 12A ± 1A | 12A ± 1A | 18A ± 1A | 12A ± 1A | 14A ± 1A | 14A ± 1A | 14A ± 1A | 
| Boost Charging Voltage | 14.4V ≤ 0.2V / Battery (12V DC of each battery) | |||||||
| Float Charging Voltage | 13.7V ≤ 0.2V / Battery (12V DC of each battery) | |||||||
| Mains Mode (Normal Mode) | ||||||||
| Input Voltage Range ± 10V | 100V – 280 V | |||||||
| Changeover Time (Mains to Backup) | < 40 ms | |||||||
| Mains Mode (UPS Mode) | ||||||||
| Input Voltage Range ± 10V | 180V – 260V | |||||||
| Changeover Time (Mains to Backup) | < 10 ms | |||||||
| Changeover Time (Backup to Mains) | < 10 ms | |||||||
| Other Features | ||||||||
| Protection | Short Circuit Trip, Overload Trip, Battery Low and Over Charge Protection, Over Temperature Protection, MCB Trip Protection, Phase Reverse Protection | |||||||
| Display | Tri Colour LCD Display which is showing: Mains Voltage, Battery Voltage, Applied Load in % Battery Charging/Charged, Battery Low/Over Charge, Short Circuit, Overload, Over Temperature | |||||||
| Dimension – L x W x H (in mm) | 330X300X168 | |||||||